收藏切换
Simulation and performance study on seismic isolation retrofit of existing 750 kV surge arrester intermediate layer
收藏切换
PDF
Chaoyi XIONG, Yun LIU, Gaoyang SHI, Qiang XIE
Earthquake Engineering and Engineering Dynamics | 2025, 45(4) : 30 - 39
Less
收藏切换
Earthquake Engineering and Engineering Dynamics | 2025, 45(4): 30-39
Simulation and performance study on seismic isolation retrofit of existing 750 kV surge arrester intermediate layer
Full
Chaoyi XIONG, Yun LIU, Gaoyang SHI, Qiang XIE
Affiliations
  • College of Civil Engineering, Tongji University, Shanghai 200092, China
Published: 2025-08-22 doi: 10.13197/j.eeed.2025.0404
Outline
收藏切换

On December 18, 2023, the Jishi mountain earthquake revealed damage to 750 kV surge arresters. In order to improve the seismic performance of existing pillar-type electrical equipment in substations, the intermediate layer was selected as the isolation part for modification. Two intermediate isolation schemes were proposed: steel wire rope damper and composite seismic isolation bearing. The original surge arrester and isolation structure were modeled using the ABAQUS finite element method. Ten sets of seismic waves were input for finite element analysis, and the stress of bushing root, top acceleration and displacement responses of each structure were extracted to compare and analyze the isolation efficiency of the intermediate layer. The results show that under seismic action, the intermediate isolation structure of the steel wire rope damper can effectively reduce the stress of bushing root and top acceleration of the surge arrester, but it has a significant amplifying effect on the top displacement, which can easily cause wire tension damage. The intermediate isolation scheme with composite seismic isolation bearing can improve the vertical stiffness of the intermediate layer structure, so that the root stress and top acceleration of the original structure bushing decrease by more than 40%, and the peak displacement of the top is only increased by 12.56%, so as to achieve a good seismic isolation effect. The intermediate isolation device with composite seismic isolation bearings exhibits good seismic isolation efficiency and is an effective retrofit measure to improve the seismic performance of existing 750 kV surge arrester.

existing structure  /  surge arrester  /  seismic isolation retrofit  /  seismic response control
Chaoyi XIONG, Yun LIU, Gaoyang SHI, Qiang XIE. Simulation and performance study on seismic isolation retrofit of existing 750 kV surge arrester intermediate layer[J]. Earthquake Engineering and Engineering Dynamics, 2025 , 45 (4) : 30 -39 . DOI: 10.13197/j.eeed.2025.0404
Year 2025 volume 45 Issue 4
PDF
61
29
Cite this Article
BibTeX
Article Info
doi: 10.13197/j.eeed.2025.0404
  • Receive Date:2024-04-26
  • Online Date:2026-03-20
  • Published:2025-08-22
Article Data
Affiliations
History
  • Received:2024-04-26
  • Revised:2024-07-01
Funding
Affiliations
    College of Civil Engineering, Tongji University, Shanghai 200092, China
References
Share
https://castjournals.cast.org.cn/joweb/dzgcygczd/EN/10.13197/j.eeed.2025.0404
Share to
QR

Scan QR to access full text

Cite this article
BibTeX
Citations
表12种不同金属材料的力学参数

Family
属数
Number of
genus
种数
Number of
species
占总种数比例
Percentage of
total species (%)

Genus
种数
Number of
species
占总种数比例
Percentage of total
species (%)
鹅膏菌科Amanitaceae 2 11 5.26 鹅膏菌属 Amanita 10 4.78
小菇科 Mycenaceae 2 12 5.74 丝盖伞属 Inocybe 5 2.39
多孔菌科 Polyporaceae 8 14 6.70 蜡蘑属 Laccaria 5 2.39
红菇科 Russulaceae 3 23 11.00 小皮伞属 Marasmius 6 2.87
小菇属 Mycena 11 5.26
光柄菇属 Pluteus 5 2.39
红菇属 Russula 17 8.13
栓菌属 Trametes 5 2.39
关闭全屏
  • BibTeX
  • EndNote
  • RefWorks
  • TxT