Effect of Dynamic Co-firing of Pulverized Coal on Load Ramp-up Capability of Circulating Fluidized Bed Power Unit
Full
Affiliations
Published: 2026-01-15 doi: 10.19805/j.cnki.jcspe.2026.240791
Outline
收藏切换
To address the technical difficulties of slow load response in circulating fluidized bed (CFB) power units due to the presence of large amounts of inert bed material on the fuel side of the boiler, a CFB power unit primarily fueled by coal gangue was focused on. A dynamic simulation model of the power unit's thermal system was established and validated, obtaining performance of key thermodynamic parameters such as output power, main steam temperature, main steam pressure, bed temperature, boiler evaporation rate and cycle efficiency during the load ramp-up process. To improve the power unit's load ramp-up capability, an optimization scheme involving dynamic co-firing of pulverized coal in the upper part of the CFB furnace was proposed to mitigate the inertial effects of coal gangue combustion. Results show that at the load ramp-up rate of 3%/min, the optimization scheme reduces the maximum deviations of output power, main steam pressure, main steam temperature, reheat steam temperature and bed temperature to 1.31%, 0.81%, 2.3 K, 3.5 K and 27.8 K respectively, all within the specified range of the DL/T 657—2015 Code for Acceptance Test of Modulating Control System in Fossil Fuel Power Plant standard. With the optimization scheme, the maximum allowable load ramp-up rate of the CFB power unit increases from 2%/min to 3%/min, while slightly improving the power unit's thermal economy.
CFB power unit  /  load ramp-up capability  /  pulverized coal  /  dynamic co-firing
. 混烧煤粉对循环流化床机组爬坡性能的影响. 动力工程学报, 2026 , 46 (1) : 19 -31 . DOI: 10.19805/j.cnki.jcspe.2026.240791
. Effect of Dynamic Co-firing of Pulverized Coal on Load Ramp-up Capability of Circulating Fluidized Bed Power Unit[J]. Journal of Chinese Society of Power Engineering, 2026 , 46 (1) : 19 -31 . DOI: 10.19805/j.cnki.jcspe.2026.240791
Year 2026 volume 46 Issue 1
77
19
Cite this Article
BibTeX
Article Info
doi: 10.19805/j.cnki.jcspe.2026.240791
  • Receive Date:2024-12-20
  • Online Date:2026-11-05
  • Published:2026-01-15
Article Data
Affiliations
History
  • Received:2024-12-20
  • Revised:2025-01-22
Funding
Affiliations
References
Share
https://castjournals.cast.org.cn/joweb/dlgcxb/EN/10.19805/j.cnki.jcspe.2026.240791
Share to
QR

Scan QR to access full text

Cite this article
BibTeX
Citations
表12种不同金属材料的力学参数
科
Family
属数
Number of
genus
种数
Number of
species
占总种数比例
Percentage of
total species (%)
属
Genus
种数
Number of
species
占总种数比例
Percentage of total
species (%)
鹅膏菌科Amanitaceae 2 11 5.26 鹅膏菌属 Amanita 10 4.78
小菇科 Mycenaceae 2 12 5.74 丝盖伞属 Inocybe 5 2.39
多孔菌科 Polyporaceae 8 14 6.70 蜡蘑属 Laccaria 5 2.39
红菇科 Russulaceae 3 23 11.00 小皮伞属 Marasmius 6 2.87
小菇属 Mycena 11 5.26
光柄菇属 Pluteus 5 2.39
红菇属 Russula 17 8.13
栓菌属 Trametes 5 2.39
关闭全屏
  • BibTeX
  • EndNote
  • RefWorks
  • TxT