To address the heat transfer deterioration caused by dust accumulation on outdoor heat exchangers of air‑source heat pumps,a visual dust removal test rig was constructed.Using mixed particles with diameters of 10 µm and 20 µm,dust removal tests were conducted on plain finned‑tube heat exchangers at different jet angles and wind speeds.Results show that under frontal horizontal jetting,when wind speed reaches 21 m/s,dust removal rate reaches 97%.Under reverse horizontal jetting at 28 m/s,dust removal rate is 40%.At 16 m/s frontal jetting speed,during the initial stage,dust removal rate increases with rising airflow angle,reaching a maximum of 94.7% at approximately 30° above horizontal.When airflow angle further increases,dust removal rate begins to decline.Dust removal mass ratio at 21 m/s frontal jetting speed also peaks around 30° at 92.9%.These findings provide important references for optimizing dust removal strategies of air‑source heat pump outdoor heat exchangers.