This study investigates performance optimization of dual‑circulation air dehumidification system by analyzing compressor operating frequency and electronic expansion valve (EEV) opening configurations. A comprehensive thermodynamic model was developed to correlate EEV openings with critical performance indicators including refrigeration capacity,refrigerant mass flow rate,coefficient of performance (COP),and dehumidification capacity. Experimental validation confirmed the optimal compressor-EEV coordination patterns under specific operating conditions. The results demonstrate that maximum COP values occur at EEV openings of 18%,25%,and 30% corresponding to compressor frequencies of 38,42,and 45 Hz respectively,revealing a monotonically increasing relationship between optimal frequency and valve opening. System optimization achieved a COP enhancement from 0.993 to 1.817 through implementation of 42 Hz compressor operation with 25% EEV opening,representing an 83% efficiency improvement. The established control strategy provides a methodological framework for operational optimization of dual‑circulation air dehumidification system under variable load conditions.