Due to the current-magnitude limit, controlled phase angle, and absence of zero-sequence current of converters, fault-location errors occur when two-phase short-circuit faults happen in offshore wind-farm collector cables. This paper analyzes the composite-sequence network under such faults and exploits the capability of both the VSC-HVDC link and the wind-turbine converters to suppress negative-sequence current during the fault. By using the locally measured negative-sequence voltage, the positive-sequence voltage at the fault point is computed on-line, a fault-distance equation is established, and the fault position is solved in real time. The proposed on-line algorithm remains accurate for large and non-resistive fault resistances and is immune to the reactive-power support strategy of the offshore wind farm, thus enhancing the safe and stable operation of offshore wind power systems.