The study on the gas production law of stator bar for hydrogenerator under high temperature and partial discharge can provide a basis for insulation ageing monitoring of hydrogenerator on the basis of decomposition gas method. Aiming at the stator bar used in hydropower station, a high temperature pyrolysis experimental platform was built to study the pyrolysis gas of stator bar at 100, 120, 150 and 250℃. A partial discharge experimental platform of stator bar was established to study the ozone generation law of stator bar under partial discharge. The results show that CO and CO2 are suitable used as the early characteristic gases of stator bar with high temperature fault. When there is partial discharge on the stator bar surface, the ozone concentration is related to discharge voltage and time. Under the same discharge condition, the ozone concentration rate generated by semi-conductive silica gel is higher and it has stronger corona resistance. Filling stator slot with semi-conductive silica gel is beneficial to the safe operation and on-line monitoring of stator bar.