The insulation resistance of the outer sheath of high-voltage cables is an important parameter for measuring the insulation state of high-voltage cables. In this paper, an online monitoring method based on metal sheath circulation current was proposed to evaluate the insulation resistance of the outer sheath of high-voltage cables, so as to realize the real-time monitoring of the insulation state of high-voltage cables. The formation of mental sheath circulation current and its relationship with the insulation resistance of outer sheath were analyzed, and a calculation model was derived. Then the online monitoring of high-voltage cable with single-end grounding and cross-linked grounding have been carried out. The results show that the error between the online monitoring method and the offline measurement method is less than 20%, and the measurement effect of the method is significantly better in the cross-linked grounding segments than in the two-sided cable segments, which is of great significance for the condition monitoring and fault location of the metal sheath of high-voltage cables.