收藏切换
Effect of thermal ageing on isothermal relaxation current and threshold electric field of distribution cable insulation
收藏切换
PDF
Ninghui HE1, Bo MA1, Weiyan SHA1, Xiuguang LI1, Pengcheng ZHANG2, Tian TIAN1
Insulating Materials | 2023, 56(8) : 51 - 57
Less
收藏切换
Insulating Materials | 2023, 56(8): 51-57
Insulation Technology
Effect of thermal ageing on isothermal relaxation current and threshold electric field of distribution cable insulation
Full
Ninghui HE1, Bo MA1, Weiyan SHA1, Xiuguang LI1, Pengcheng ZHANG2, Tian TIAN1
Affiliations
  • 1Power Research Institute of State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750002, China
  • 2Shizuishan Power Supply Company of State Grid Ningxia Electric Power Co., Ltd., Shizuishan 753099, China
Published: 2023-08-20 doi: 10.16790/j.cnki.1009-9239.im.2023.08.008
Outline
收藏切换

In view of the problem and difficulty of isothermal relaxation current method in evaluating the insulation state of distribution cables, a new sample of domestic unaged 10 kV distribution cable was used as the test object in this paper, and the isothermal relaxation current of the cable section and the high-field conductance current of the insulation slice during the 288 hours of accelerated thermal ageing process at 140℃ were detected. The variation trend and range of current relaxation component, ageing factor A, and threshold electric field Et during thermal ageing were analyzed. The results show that there are three obvious polarization relaxation peaks in the isothermal relaxation current, and the time constants τ1, τ2, and τ3 are in the range of 7-12 s, 31-39 s, and 210-536 s, respectively. During the thermal ageing process, the material traps corresponding to isothermal relaxation current Peak2 and Peak3 change greatly, and the change of Peak3 is the most obvious. The ageing factor A based on the isothermal relaxation current is in the range of 1.72-3.17. The A decreases at first and then increases with the increase of ageing time, and the corresponding conductance threshold electric field Et shows the opposite trend of rising at first and then decreasing, which indicates that there is a clear correlation between the threshold electric field Et and the ageing factor A, they are both the macroscopic appearances of internal molecular structure of the insulating material. The ageing factor A of the domestic cable before ageing is 1.91, which is close to the "aged" state of the German standard DIN VDE 0276, and the A drops to 1.72 after ageing for 48 h, which reaches the "better" state of the German standard. The high A of the domestic cable may be related to the residues of cross-linking by-products of cables, so the degassing process should be improved in the production of domestic cables.

distribution cable  /  thermal ageing  /  isothermal relaxation current  /  high field conductivity  /  ageing factor threshold electric field
Ninghui HE, Bo MA, Weiyan SHA, Xiuguang LI, Pengcheng ZHANG, Tian TIAN. Effect of thermal ageing on isothermal relaxation current and threshold electric field of distribution cable insulation[J]. Insulating Materials, 2023 , 56 (8) : 51 -57 . DOI: 10.16790/j.cnki.1009-9239.im.2023.08.008
Year 2023 volume 56 Issue 8
PDF
151
68
Cite this Article
BibTeX
Article Info
doi: 10.16790/j.cnki.1009-9239.im.2023.08.008
  • Receive Date:2022-08-25
  • Online Date:2025-11-24
  • Published:2023-08-20
Article Data
Affiliations
History
  • Received:2022-08-25
  • Revised:2022-10-17
Funding
Affiliations
    1Power Research Institute of State Grid Ningxia Electric Power Co., Ltd., Yinchuan 750002, China
    2Shizuishan Power Supply Company of State Grid Ningxia Electric Power Co., Ltd., Shizuishan 753099, China
References
Share
https://castjournals.cast.org.cn/joweb/jycl/EN/10.16790/j.cnki.1009-9239.im.2023.08.008
Share to
QR

Scan QR to access full text

Cite this article
BibTeX
Citations
表12种不同金属材料的力学参数

Family
属数
Number of
genus
种数
Number of
species
占总种数比例
Percentage of
total species (%)

Genus
种数
Number of
species
占总种数比例
Percentage of total
species (%)
鹅膏菌科Amanitaceae 2 11 5.26 鹅膏菌属 Amanita 10 4.78
小菇科 Mycenaceae 2 12 5.74 丝盖伞属 Inocybe 5 2.39
多孔菌科 Polyporaceae 8 14 6.70 蜡蘑属 Laccaria 5 2.39
红菇科 Russulaceae 3 23 11.00 小皮伞属 Marasmius 6 2.87
小菇属 Mycena 11 5.26
光柄菇属 Pluteus 5 2.39
红菇属 Russula 17 8.13
栓菌属 Trametes 5 2.39
关闭全屏
  • BibTeX
  • EndNote
  • RefWorks
  • TxT