收藏切换
Study on Failure Mechanism of 35 kV Prefabricated Cable Terminal Under Impulse Voltage
收藏切换
PDF
Shuning XIE, Ming SUN, Lei ZHANG, Kang SUN, Zhousheng ZHANG
Insulating Materials | 2022, 55(10) : 54 - 60
Less
收藏切换
Insulating Materials | 2022, 55(10): 54-60
Insulation Technology
Study on Failure Mechanism of 35 kV Prefabricated Cable Terminal Under Impulse Voltage
Full
Shuning XIE, Ming SUN, Lei ZHANG, Kang SUN, Zhousheng ZHANG
Affiliations
  • Shanghai University of Electric Power, Shanghai 200090, China
Published: 2022-10-20 doi: 10.16790/j.cnki.1009-9239.im.2022.10.009
Outline
收藏切换

The simulation model of 35 kV prefabricated cable terminal was established to simulate and calculate the electric stress, thermal stress, and mechanical stress distribution of the cable terminal under the impulse voltage. The electric field, temperature, and stress of body insulation, semi-conductive layer, and shielding layer were calculated and analyzed, and the influence of harmonic wave with different frequency on the electric field distribution was considered. The results show that the influence of high frequency signal on permittivity does not lead to large distortion of electric field intensity, and the change of electric field intensity is not obvious. At the same time, the temperature rise of cable terminal caused by impulse voltage is small, and its influence can be ignored. The impulse voltage increases the mechanical stress at the intersection of the semi-conductive layer and the stress cone, and the maximum radial strain reaches to 2.54%, which makes the position of the semi-conductive layer prone to produce air gap and is the main cause of cable terminal damage. It is concluded that not only the electric field optimization but also the elastic strain of the material should be considered in the material selection and structural design.

impulse voltage  /  cable terminal  /  electric field distribution  /  mechanical stress
Shuning XIE, Ming SUN, Lei ZHANG, Kang SUN, Zhousheng ZHANG. Study on Failure Mechanism of 35 kV Prefabricated Cable Terminal Under Impulse Voltage[J]. Insulating Materials, 2022 , 55 (10) : 54 -60 . DOI: 10.16790/j.cnki.1009-9239.im.2022.10.009
Year 2022 volume 55 Issue 10
PDF
161
73
Cite this Article
BibTeX
Article Info
doi: 10.16790/j.cnki.1009-9239.im.2022.10.009
  • Receive Date:2021-10-10
  • Online Date:2025-12-23
  • Published:2022-10-20
Article Data
Affiliations
History
  • Received:2021-10-10
  • Revised:2021-11-30
Funding
Affiliations
    Shanghai University of Electric Power, Shanghai 200090, China
References
Share
https://castjournals.cast.org.cn/joweb/jycl/EN/10.16790/j.cnki.1009-9239.im.2022.10.009
Share to
QR

Scan QR to access full text

Cite this article
BibTeX
Citations
表12种不同金属材料的力学参数

Family
属数
Number of
genus
种数
Number of
species
占总种数比例
Percentage of
total species (%)

Genus
种数
Number of
species
占总种数比例
Percentage of total
species (%)
鹅膏菌科Amanitaceae 2 11 5.26 鹅膏菌属 Amanita 10 4.78
小菇科 Mycenaceae 2 12 5.74 丝盖伞属 Inocybe 5 2.39
多孔菌科 Polyporaceae 8 14 6.70 蜡蘑属 Laccaria 5 2.39
红菇科 Russulaceae 3 23 11.00 小皮伞属 Marasmius 6 2.87
小菇属 Mycena 11 5.26
光柄菇属 Pluteus 5 2.39
红菇属 Russula 17 8.13
栓菌属 Trametes 5 2.39
关闭全屏
  • BibTeX
  • EndNote
  • RefWorks
  • TxT