To deal with the over-voltage increase at the point of common coupling by the reactive power of a static synchronous compensator (STATCOM) due to its slow response speed when the grid voltage changes rapidly, a general criteria and technical indicators characterizing the over-voltage increase were proposed. Through a simplified analysis based on the magnitude of fundamental voltage, the severity of this over-voltage increase problem due to the slow response speed of STACOM was shown, and the quantitative requirement for calculating the AC voltage became clear. A fast voltage algorithm based on second-order generalized integrator and the corresponding coordination strategy were put forward. The main circuit topology of a STATCOM from a practical project and its control strategy were applied, and the digital simulation results from both a simplified Thevenin’s equivalent circuit and a complicated HVDC benchmark system showed that the proposed fast algorithm and coordination strategy can solve the over-voltage increase problem.