Harmonic pollution is one of the key problems restricting the grid connection of new energy sources. There are many factors that lead to an increase in current harmonics of grid-connected inverters, including the harmonic voltage of the grid and the sampling error of voltage and current signals in the grid-connected inverter system. On the basis, the principle of voltage sampling error and current sampling error of the grid-connected inverter system affecting the 2nd-order harmonic current of the inverter is analyzed, and a 2nd-order harmonic current suppression method based on high-precision harmonic sampling and 2nd-order harmonic current three-phase double-frequency rotation dq feedback is studied. In addition, a model of the 2nd-order harmonic current suppression loop is established, a design method for the parameters of the 2nd-order harmonic current suppression loop is given, and the expression of suppression effect is deduced. Finally, the proposed method was verified by experimental results of a 100 kW prototype.