In the impedance measurement process, since the inverter impedance varied widely, the magnitude of injection disturbance cannot be evaluated in advance. Therefore, it is necessary to adjust the disturbance energy adaptively. The impedance measurement device of disturbance voltage injected in series is taken as the research object, and an adaptive adjustment strategy of disturbance voltage based on disturbance current feedback is proposed. The magnitude of disturbance voltage is adjusted by detecting the responding disturbance current in real time, thus realizing the adaptive adjustment of disturbance energy. Both the disturbance voltage and responding disturbance current are controlled to be within 10% of the steady-state point of the system under test. The effectiveness of the proposed control strategy was verified by hardware-in-the-loop simulations in real time.