收藏切换
Adaptive Active Arc Suppression Method for Single Phase Grounding in Distribution Network Based on S-transform Correlation Degree
收藏切换
PDF
Yunwang LI, Junde CHEN, Daping ZHANG, Yun SANG, Xiaolei HAN
Electric Drive | 2024, 54(7) : 86 - 92
Less
收藏切换
Electric Drive | 2024, 54(7): 86-92
Adaptive Active Arc Suppression Method for Single Phase Grounding in Distribution Network Based on S-transform Correlation Degree
Full
Yunwang LI, Junde CHEN, Daping ZHANG, Yun SANG, Xiaolei HAN
Affiliations
  • State Grid Xining Power Supply Company,Xining 810003,Qinghai,China
Published: 2024-07-20 doi: 10.19457/j.1001-2095.dqcd24937
Outline
收藏切换

An adaptive active arc suppression method based on S-transform correlation degree for distribution network unidirectional grounding was proposed to effectively eliminate single-phase grounding fault arc in distribution network and improve power system stability. The time series data of zero-sequence current of distribution network lines were collected,the time-frequency information matrix of zero-sequence current through S-transformation was obtained,the correlation matrix of time-frequency information matrix between each line was calculated and obtained. Input the convolution neural network model,and output the single-phase grounding fault line selection results;the double closed-loop adaptive control method based on fuzzy quasi-PR and PI control was adopted in the fault line to inject zero-sequence current into the neutral point of the fault line of the distribution network,effectively control the phase and amplitude of the injected current,force the voltage value of the phase of the fault line of the distribution network to be 0,and complete the adaptive active arc suppression. The experimental results show that this method can effectively identify the single-phase grounding fault lines in the distribution network,realize the single-phase grounding adaptive active arc suppression,and complete the single-phase grounding adaptive active arc suppression work as soon as possible to ensure the safe and stable operation of the distribution network.

S-transformation  /  correlation degree  /  distribution network  /  single phase grounding fault  /  adaptive  /  active arc suppression
Yunwang LI, Junde CHEN, Daping ZHANG, Yun SANG, Xiaolei HAN. Adaptive Active Arc Suppression Method for Single Phase Grounding in Distribution Network Based on S-transform Correlation Degree[J]. Electric Drive, 2024 , 54 (7) : 86 -92 . DOI: 10.19457/j.1001-2095.dqcd24937
Year 2024 volume 54 Issue 7
PDF
157
68
Cite this Article
BibTeX
Article Info
doi: 10.19457/j.1001-2095.dqcd24937
  • Receive Date:2023-02-06
  • Online Date:2025-12-09
  • Published:2024-07-20
Article Data
Affiliations
History
  • Received:2023-02-06
  • Revised:2023-03-10
Affiliations
    State Grid Xining Power Supply Company,Xining 810003,Qinghai,China
References
Share
https://castjournals.cast.org.cn/joweb/dqcd/EN/10.19457/j.1001-2095.dqcd24937
Share to
QR

Scan QR to access full text

Cite this article
BibTeX
Citations
表12种不同金属材料的力学参数

Family
属数
Number of
genus
种数
Number of
species
占总种数比例
Percentage of
total species (%)

Genus
种数
Number of
species
占总种数比例
Percentage of total
species (%)
鹅膏菌科Amanitaceae 2 11 5.26 鹅膏菌属 Amanita 10 4.78
小菇科 Mycenaceae 2 12 5.74 丝盖伞属 Inocybe 5 2.39
多孔菌科 Polyporaceae 8 14 6.70 蜡蘑属 Laccaria 5 2.39
红菇科 Russulaceae 3 23 11.00 小皮伞属 Marasmius 6 2.87
小菇属 Mycena 11 5.26
光柄菇属 Pluteus 5 2.39
红菇属 Russula 17 8.13
栓菌属 Trametes 5 2.39
关闭全屏
  • BibTeX
  • EndNote
  • RefWorks
  • TxT